The KL06 230V wiring center is designed to manage SALUS heating systems. It supports up to 6 zones and can work with actuators and pump/boiler modules. If the unit does not show any power indicators (no green "Power" LED), a structured diagnosis should be performed.
The green power LED is off.
Fuse and 230V power supply have been confirmed as functional.
Check voltage directly at the L/N terminals of the KL06 using a multimeter.
Faulty wiring or power source may be the cause.
Solution:
Disconnect power.
Remove the top cover and check for loose or damaged wires inside.
Ensure all terminal screws are tight and wires are properly inserted.
Step | Action | Expected Result |
1. | Measure voltage at L/N terminals | 230V AC present |
2. | Check the T2A fuse | Replace it even if it looks intact |
3. | Open cover and inspect wiring | Wires are tight and properly connected |
4. | Reconnect power | Green "Power" LED should light up |
Symptom | Possible Cause | Suggested Fix |
No power at all | No voltage, blown fuse, loose L/N connection | Verify voltage, replace fuse |
Power LED off, system works | Burnt LED but device still operates | Confirm with actuator/thermostat response |
Some zones not working | Incorrect wiring or overloading zone output | Check zone load and wiring |
Actuators not responding | KL06 working but not sending output to actuators | Output failure – possible short or overload |
Connect only the 230V L/N power supply.
Connect one 230V thermostat (e.g. SQ610) to zone 1.
Connect one actuator (e.g. T30NC) to zone 1.
Power on the unit – observe power LED and actuator response.
Model: KL06 230V
Power supply: 230V AC / 50Hz
Fuse: T2A (5x20mm, slow-blow)
Outputs: Up to 6 thermostats, max. 4 actuators per zone (24 total)